JAB Detektor dima i povišene temperatura, BUS JA-110ST View larger

Smoke and temperature detector JA-110ST

JA-110ST

New product

JABLOTRON ALARMS S.A.

JA-110ST is an addressable BUS combined smoke and heat detector for indoor fire detection. Powered from the control panel BUS 12 V (9–15 V), it offers configurable detection modes (optical and/or thermal), SMART MEMORY LED, tamper reporting and low quiescent current (5 mA).

More details

Data sheet

Connection method BUS

More info

JA-110ST is an addressable BUS combined smoke and temperature detector that integrates an optical smoke chamber with a heat sensor. It is intended for early fire detection in residential and commercial interiors and allows selection of response modes: optical and thermal together, optical only or thermal only.

The detector occupies one address on the digital BUS and is assigned during enrolment. SMART MEMORY INDICATION (SMI) provides a visual LED confirmation of past activations; SMI behaviour can be controlled or disabled via the system software.

The device reports a tamper when the cover is opened (unless the control panel is in Service mode). Installation, enrolment and configuration must be performed by a qualified installer following recommended placement rules (typically ceiling mounting and appropriate distances from walls and ventilation) to minimise false alarms.

Testing and maintenance

The optical function can be checked with a test spray and the heat function with a suitable heat source; if both triggers are enabled, combined testing is required. Monthly functional tests and regular cleaning of the detector cover and vents from dust and cobwebs are recommended to ensure reliable operation.

Technical specifications

  • Power: from control panel digital BUS 12 V (9…15 V)
  • Quiescent current: 5 mA; maximal current: 10 mA
  • Dimensions: diameter 126 mm, height 50 mm; weight: 143 g
  • Smoke detection: optical light scattering; sensitivity m = 0.11 ÷ 0.13 dB/m (EN 54‑7)
  • Heat detection: class A2 (EN 54‑5); alarm temperature +60 °C to +70 °C
  • Operating temperature: -10 °C to +80 °C; humidity: up to 75 % non‑condensing
  • Standards: EN 54‑5, EN 54‑7, EN 50130‑4, EN 55032, EN 50581

JA-110ST is intended for use in JABLOTRON 100 systems and is compatible with control units such as JA-101K, JA-102K, JA-103K, JA-106K and JA-107K. For correct placement, enrolment and configuration follow the manufacturer's installation instructions.

Download

30 other products in the same category:

Follow us on Facebook